Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2021, 07:38 AM
  • B 0365_B 0364_07202021_005038.mp4

Date
07/20/2021
W/O
901610
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00091
PipeID
P08877
Time
12:38 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9038
Sewer Name
B JOINT OUTFALL B - UNIT 5A
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
10
Purpose
Routine Assessment
Project
WO_901610_TV15051_JUL2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
63 in.
Upstream MH
B 0365
Downstream MH
B 0364
Dir. of Survey
Downstream
Length Surveyed
287.8 ft.
Total Length
287.8 ft.
Structural Index
2
Structural Quick
3J2J
Structural Rating
269
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
273
Pipe schematic from manhole B 0365 to B 0364
MH: B 0365MH: B 0364downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 03650 ft. MGO - General Observation - COCKROACHES IN MANHOLE3.4 ft. MGO - General Observation - MAG COATING THROUGHOUT11.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start18.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start285.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE285.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish285.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish287.8 ft. AMH - Downstream Manhole, Survey Ends - B 0364

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - MAG COATING THROUGHOUT

    3.4 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    11.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    18.3 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    285.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
285.2MGOCOCKROACHES IN MANHOLE
18.3SAP
11.1SSS
0MWL
0MWM
3.4MGOMAG COATING THROUGHOUT
287.8AMHB 0364
0AMHB 0365
285.2SAP
0MGOCOCKROACHES IN MANHOLE
285.2SSS

Properties (7)

additional_info
630069071921201
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-07-20T00:38:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false