Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 30, 2021, 05:27 PM
  • 3_1_1_30072021_115602.mp4

Date
07/30/2021
W/O
0896127
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00878
PipeID
P17736
Time
10:27 AM
Certificate
U-415-06024039
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0373
Sewer Name
SOUTH BAY CITIES MAIN TRUNK
City
HERMOSA BEACH
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20210730DF__SOUTH_BAY_CITIES_MAIN_TRUNK
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
30 0033
Downstream MH
30 0032
Dir. of Survey
Downstream
Length Surveyed
387.9 ft.
Total Length
387.9 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
385
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
385
Pipe schematic from manhole 30 0033 to 30 0032
MH: 30 0033MH: 30 0032downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 11:54 AM0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 70% MAG COAT2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN94.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN128.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"161.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN195.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN228.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN385.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish385.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish387.9 ft. AMH - Downstream Manhole, Survey Ends - 12:15 PM

Observations (16)

DistanceCodeObservation
195.2TFUNKNOWN
2SSS
61.7TFUNKNOWN
385.7SSS
228.8TFUNKNOWN
0MWL
2MGO70% MAG COAT
128.4TFC
0AMH11:54 AM
387.9AMH12:15 PM
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
2SAP
94.5TFUNKNOWN
0MWM
385.7SAP
161.5TFUNKNOWN

Properties (6)

custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-07-30T10:27:29-07:00
documentation
FRANKLIN, IGNACIO, CASTILLO, RUVALCABA
is_lateral_inspection
false