Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2021, 06:19 AM
  • 05 1272_05 1271_06172021_232725.mp4

Date
06/17/2021
W/O
896358
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00518
PipeID
P06484
Time
11:19 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8988
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_896358_TV05332_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
05 1272
Downstream MH
05 1271
Dir. of Survey
Downstream
Length Surveyed
177.4 ft.
Total Length
177.4 ft.
Structural Index
3
Structural Quick
4E3F
Structural Rating
295
O&M Index
2
O&M Quick
2F00
O&M Rating
70
Overall Index
3
Overall Quick
Overall Rating
365
Pipe schematic from manhole 05 1272 to 05 1271
MH: 05 1272MH: 05 1271downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKONWN0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 12722 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.7 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES34.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start62 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"64.1 ft. TSA - Tap Saddle Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"102.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN132.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"175 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish175 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish175 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish177.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish177.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1271

Observation photos (5)

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    5.7 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    34.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"

    62 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"

  • Tap Saddle Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"

    64.1 ft. - Tap Saddle Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    102.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

Observations (18)

DistanceCodeObservation
177.4AMH05 1271
34.6FM
2SSS
62TBA
177.3FM
2DAGS
2CM
102.6TBOPEN
0MWL
0MGOCONN @ MH 3 O'CLOCK/UNKONWN
175CM
175SSS
132.4TFC
0MWM
5.7FM
175DAGS
64.1TSA
0AMH05 1272

Properties (7)

additional_info
630074061721201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-06-17T23:19:27-07:00
documentation
PROPIPE
is_lateral_inspection
false