Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2021, 07:07 AM
  • 05 1268_05 1267_06182021_001337.mp4

Date
06/18/2021
W/O
896358
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00518
PipeID
P06480
Time
12:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8988
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_896358_TV05332_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
05 1268
Downstream MH
05 1267
Dir. of Survey
Downstream
Length Surveyed
130.1 ft.
Total Length
130.1 ft.
Structural Index
3
Structural Quick
3D2D
Structural Rating
125
O&M Index
2
O&M Quick
2D00
O&M Rating
52
Overall Index
2
Overall Quick
Overall Rating
177
Pipe schematic from manhole 05 1268 to 05 1267
MH: 05 1268MH: 05 1267downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 12680 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start55.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"63.2 ft. TSI - Tap Saddle Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 1" - OPEN119.3 ft. TSC - Tap Saddle Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish128 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish130 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE130 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish130.1 ft. AMH - Downstream Manhole, Survey Ends - 05 1267

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 1" - OPEN

    63.2 ft. - Tap Saddle Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 1" - OPEN

Observations (15)

DistanceCodeObservation
0AMH05 1268
2CM
0MWM
130MGOCONN @ MH 9 O'CLOCK/ACTIVE
119.3TSC
55.6TFC
2DAGS
130.1AMH05 1267
0MWL
128SSS
128DAGS
2SSS
63.2TSIOPEN
130CM
0.1MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (7)

additional_info
630074061721201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-18T00:07:03-07:00
documentation
PROPIPE
is_lateral_inspection
false