Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2021, 10:15 AM
  • 05 1263_05 1262_06172021_032701.mp4

Date
06/17/2021
W/O
896358
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00518
PipeID
P06474
Time
3:15 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8987
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_896358_TV05332_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
05 1262
Downstream MH
05 1263
Dir. of Survey
Upstream
Length Surveyed
340.6 ft.
Total Length
340.6 ft.
Structural Index
3
Structural Quick
513L
Structural Rating
340
O&M Index
2
O&M Quick
2L1H
O&M Rating
179
Overall Index
2
Overall Quick
Overall Rating
519
Pipe schematic from manhole 05 1262 to 05 1263
MH: 05 1262MH: 05 1263upstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 05 12630.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish42 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish70.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN128.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN194.9 ft. B - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES195.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN195.3 ft. RFL - Roots Fine Lateral, at 10 o'clock - 5% ROOTS263.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start271.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"296.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"325.6 ft. MWM - Water Mark, 15 %of cross sectional area334.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start338.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start338.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start340.6 ft. MWL - Water Level, 10 %of cross sectional area340.6 ft. MWM - Water Mark, 15 %of cross sectional area340.6 ft. MGO - General Observation - ROACHES @ MH340.6 ft. AMH - Downstream Manhole, Survey Begins - 05 1262

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    77.1 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    145.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

    145.7 ft. - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    211.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

Observations (23)

DistanceCodeObservation
298.6RFJ
266.3TFOPEN
211.8TBOPEN
340.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
338SSS
77.1RFJ
0MWL
2SSS
0MWM
44.2TFC
69.1TFC
340.4CM
145.3TBOPEN
145.7B
5.8CM
2DAGS
0MGOROACHES @ MH
269.7TFC
145.3RFL5% ROOTS
340.6AMH05 1263
0AMH05 1262
15MWM
338DAGS

Properties (7)

additional_info
630074061621202
custom_field_three
MULTIPLE CRACKS/FRACTURE
custom_field_two
3
customer
1
datetime
2021-06-17T03:15:11-07:00
documentation
PROPIPE
is_lateral_inspection
false