Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2021, 05:06 AM
  • 05 1256_05 1255_06172021_221840.mp4

Date
06/17/2021
W/O
896358
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00518
PipeID
P06464
Time
10:06 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8988
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_896358_TV05332_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
24 in.
Upstream MH
05 1256
Downstream MH
05 1255
Dir. of Survey
Downstream
Length Surveyed
399.9 ft.
Total Length
399.9 ft.
Structural Index
2
Structural Quick
322O
Structural Rating
164
O&M Index
2
O&M Quick
2O11
O&M Rating
161
Overall Index
2
Overall Quick
Overall Rating
325
Pipe schematic from manhole 05 1256 to 05 1255
MH: 05 1256MH: 05 1255downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 12560 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start48.1 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - ACTIVE165.9 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES397 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish397 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish397 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish399.9 ft. AMH - Downstream Manhole, Survey Ends - 05 1255399.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED399.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - ACTIVE

    48.1 ft. - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - ACTIVE

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES

    165.9 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
2SSS
0AMH05 1256
165.9RFJ
397DAGS
0MWM
399.9AMH05 1255
397CM
397SSS
2CM
48.1TBIACTIVE
2DAGS
399.9MGOCONN @ MH 3 O'CLOCK/CAPPED
399.9MGOCONN @ MH 9 O'CLOCK/CAPPED
0MGOCONN @ MH 3 O'CLOCK/CAPPED
0MGOCONN @ MH 9 O'CLOCK/CAPPED
0MWL

Properties (7)

additional_info
630074061721201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-17T22:06:49-07:00
documentation
PROPIPE
is_lateral_inspection
false