Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2021, 07:35 AM
  • 18 0035_18 0034_06222021_005121.mp4

Date
06/22/2021
W/O
896583
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00713
PipeID
P13851
Time
12:35 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8534
Sewer Name
18 WALNUT WAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
15
Purpose
Routine Assessment
Project
RFIR_WO_896583_TV18059_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0034
Downstream MH
18 0035
Dir. of Survey
Upstream
Length Surveyed
319.4 ft.
Total Length
319.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0034 to 18 0035
MH: 18 0034MH: 18 0035upstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Ends - 18 00350 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish3 ft. MGO - General Observation - MAG COATING END73.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"79.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"127.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"146.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"164.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"170 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"172.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"197.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"236.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"248.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"288.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"312.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"317.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start319.4 ft. MWM - Water Mark, 15 %of cross sectional area319.4 ft. AMH - Downstream Manhole, Survey Begins - 18 0034319.4 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
0MWM
82.5TF
319.4MGOCONNECTION AT THE MH 9 OC'LOCK
149.4TBA
70.9TFC
191.6TB
316.4SAV
0AMH18 0034
173.3TFC
6.7TFA
0MWL
31TFC
121.7TF
319.4AMH18 0035
155TF
240.1TF
2.3SAV
246TFC
316.4MGOMAG COATING END
146.7TB
319.4MGOCONNECTION AT THE MH 3 OC'LOCK

Properties (7)

additional_info
630074062121201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-06-22T00:35:01-07:00
documentation
PROPIPE
is_lateral_inspection
false