Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2021, 07:13 AM
  • 18 0034_18 0033_06222021_003433.mp4

Date
06/22/2021
W/O
896583
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00713
PipeID
P13850
Time
12:13 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8534
Sewer Name
18 WALNUT WAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
15
Purpose
Routine Assessment
Project
RFIR_WO_896583_TV18059_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0033
Downstream MH
18 0034
Dir. of Survey
Upstream
Length Surveyed
314.4 ft.
Total Length
314.4 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
186
Pipe schematic from manhole 18 0033 to 18 0034
MH: 18 0033MH: 18 0034upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 00342.8 ft. MGO - General Observation - MAG COATING END2.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish18.6 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"24.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"73.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"79.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"124.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"130.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"167.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"170 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"172.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"227.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"257.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"284.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"312.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start312.4 ft. MGO - General Observation - MAG COAT314.4 ft. MWM - Water Mark, 15 %of cross sectional area314.4 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK314.4 ft. MWL - Water Level, 5 %of cross sectional area314.4 ft. AMH - Downstream Manhole, Survey Begins - 18 0033

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

Observations (21)

DistanceCodeObservation
146.8TF
0MWM
289.6TFC
0MGOCONNECTION AT THE MH 9 OC'LOCK
241.1TFC
0MWL
141.5TFC
295.8TBA
311.6MGOMAG COATING END
184.1TF
2SAV
86.8TFC
314.4AMH18 0034
0AMH18 0033
56.5TFA
29.8TFC
311.5SAV
190TFC
2MGOMAG COAT
235.3TF
144.4TFC

Properties (7)

additional_info
630074062121201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-06-22T00:13:32-07:00
documentation
PROPIPE
is_lateral_inspection
false