Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 21, 2021, 09:52 AM
  • 01 1316_01 0031_07212021_030021.mp4

Date
07/21/2021
W/O
901576
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00209
PipeID
P01614
Time
2:52 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8684
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
WO_901576_TV01040_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
12 in.
Upstream MH
01 1316
Downstream MH
01 0031
Dir. of Survey
Downstream
Length Surveyed
179.5 ft.
Total Length
179.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 01 1316 to 01 0031
MH: 01 1316MH: 01 0031downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 13162.2 ft. MGO - General Observation - LINED PIPE3.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start177.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish179.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0031

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    3.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWL
179.5AMH01 0031
0MWM
0AMH01 1316
2.2MGOLINED PIPE
177.8DAGS
3.4DAGS

Properties (8)

additional_info
630138072021202
custom_field_three
LINED PIPE
custom_field_two
4
customer
1
datetime
2021-07-21T02:52:39-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP