Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 6, 2017, 11:10 AM
  • 05 0778_05 0777 _06032017_031039.mp4

Date
03/06/2017
W/O
624365
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00553
PipeID
P06006
Time
3:10 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4367
Sewer Name
05 MANCHESTER-VERMONT DIVERSION EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_624365_TV05272_MAR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0777
Downstream MH
05 0778
Dir. of Survey
Upstream
Length Surveyed
395.2 ft.
Total Length
395.2 ft.
Structural Index
4
Structural Quick
4N33
Structural Rating
305
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
305
Pipe schematic from manhole 05 0777 to 05 0778
MH: 05 0777MH: 05 0778upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 07782.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish369.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start369.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish386.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start390.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES395.2 ft. MWM - Water Mark, 20 %of cross sectional area395.2 ft. AMH - Downstream Manhole, Survey Begins - 05 0777395.2 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    25.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
9CM
25.6FM
25.6CM
395.2AMH05 0778
0MWM
393.1FM
0AMH05 0777
0MWL
4.8FM

Properties (6)

additional_info
SC306878
custom_field_two
2
customer
LACSD
datetime
2017-03-06T03:10:22-08:00
documentation
PROPIPE
is_lateral_inspection
false