Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 20, 2017, 05:38 PM
  • J 0267_J 0266_02132017_023846.mpg

Date
01/20/2017
W/O
619078
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00059
PipeID
P11506
Time
9:38 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4264
Sewer Name
J JOINT OUTFALL J - UNIT 1G
City
PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
46
Purpose
Routine Assessment
Project
WO_619078_TV05169_FEB2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
J 0267
Downstream MH
J 0266
Dir. of Survey
Downstream
Length Surveyed
284.8 ft.
Total Length
284.8 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
168
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
3
Overall Quick
Overall Rating
280
Pipe schematic from manhole J 0267 to J 0266
MH: J 0267MH: J 0266downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 02670 ft. MWM - Water Mark, 25 %of cross sectional area3.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start284.8 ft. AMH - Downstream Manhole, Survey Ends - J 0266284.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish284.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish284.8 ft. MGO - General Observation - CONNECTION AT 9 O CLOCK

Observations (9)

DistanceCodeObservation
0MWL
0AMHJ 0267
3.2SAV
284.8AMHJ 0266
0MWM
284.8SAV
284.8DAGS
3.2DAGS
284.8MGOCONNECTION AT 9 O CLOCK

Properties (6)

additional_info
SC318715
custom_field_two
3
customer
LACSD
datetime
2017-01-20T09:38:09-08:00
documentation
PRO PIPE
is_lateral_inspection
false