Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 20, 2017, 05:38 PM
  • J 0266_J 0265_02132017_025924.mpg

Date
01/20/2017
W/O
619078
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00059
PipeID
P11505
Time
9:38 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4264
Sewer Name
J JOINT OUTFALL J - UNIT 1G
City
PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
46
Purpose
Routine Assessment
Project
WO_619078_TV05169_FEB2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
J 0266
Downstream MH
J 0265
Dir. of Survey
Downstream
Length Surveyed
286.2 ft.
Total Length
286.2 ft.
Structural Index
1
Structural Quick
1J00
Structural Rating
57
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
171
Pipe schematic from manhole J 0266 to J 0265
MH: J 0266MH: J 0265downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 02663.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start3.6 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: NO, Start3.6 ft. MGO - General Observation - MAG COATING106.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"170.8 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 4"286.2 ft. MGO - General Observation - CONNECTION AT 9 O CLOCK286.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish286.2 ft. AMH - Downstream Manhole, Survey Ends - J 0265286.2 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish

Observation photos (1)

  • Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    3.6 ft. - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

Observations (12)

DistanceCodeObservation
170.8TB
286.2MGOCONNECTION AT 9 O CLOCK
0MWL
3.6DAGS
3.6SRI
106.3TB
286.2DAGS
286.2AMHJ 0265
0MWM
286.2SRI
3.6MGOMAG COATING
0AMHJ 0266

Properties (6)

additional_info
SC318715
custom_field_two
4
customer
LACSD
datetime
2017-01-20T09:38:09-08:00
documentation
PRO PIPE
is_lateral_inspection
false