Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2017, 07:19 AM
  • J 0302_J 0301_02012017_233053.mpg

Date
02/01/2017
W/O
619078
Weather
Dry
Operator/Surveyor
R,VARGAS
Sewer ID
Z00059
PipeID
P11543
Time
11:19 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4103
Sewer Name
J JOINT OUTFALL J - UNIT 1G
City
RANCHO PALOS VERDES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
41
Purpose
Routine Assessment
Project
WO_619078_TV05169_FEB2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
J 0302
Downstream MH
J 0301
Dir. of Survey
Downstream
Length Surveyed
139.3 ft.
Total Length
139.3 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
81
O&M Index
2
O&M Quick
2E00
O&M Rating
56
Overall Index
2
Overall Quick
Overall Rating
137
Pipe schematic from manhole J 0302 to J 0301
MH: J 0302MH: J 0301downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 03020 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE2.1 ft. MGO - General Observation - MAGNESIUM H.O. START2.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start78.1 ft. MGP - General Photograph125.3 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 04 to 08 o'clock - DEBRIS NOT VISIBLE136.1 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH136.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish136.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish139.3 ft. AMH - Downstream Manhole, Survey Ends - J 0301

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    78.1 ft. - General Photograph

Observations (13)

DistanceCodeObservation
136.1MGOMAGNEZIUM H.O. FINISH
0MWM
125.3OBZDEBRIS NOT VISIBLE
136.1SAV
0AMHJ 0302
78.1MGP
2.1MGOMAGNESIUM H.O. START
136.1DAGS
139.3AMHJ 0301
2.1DAGS
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
2.1SAV

Properties (6)

additional_info
SC318645
custom_field_two
3
customer
LACSD
datetime
2017-02-01T23:19:46-08:00
documentation
PRO PIPE
is_lateral_inspection
false