Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 12, 2021, 09:41 AM
  • 02 1546A_02 1546_07122021_024808.mp4

Date
07/12/2021
W/O
901516
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00230
PipeID
P03978
Time
2:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9069
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 1
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_901516_TV02006_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
15 in.
Upstream MH
02 1546A
Downstream MH
02 1546
Dir. of Survey
Downstream
Length Surveyed
136.8 ft.
Total Length
136.8 ft.
Structural Index
2
Structural Quick
3321
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 02 1546A to 02 1546
MH: 02 1546AMH: 02 1546downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 1546A0 ft. MWM - Water Mark, 20 %of cross sectional area7.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES24.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"47.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"49.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"97.8 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"103.7 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"123.1 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES125.1 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES128.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES136.8 ft. AMH - Downstream Manhole, Survey Ends - 02 1546

Observation photos (2)

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    97.8 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    103.7 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

Observations (14)

DistanceCodeObservation
97.8TB
128.1CM
125.1CC
103.7TB
0MGOCONNECTION AT THE MH 9 OC'LOCK
123.1CM
136.8AMH02 1546
47.1TFC
0MWL
24.6TFC
0AMH02 1546A
0MWM
49.9TFC
7.7CL

Properties (7)

additional_info
NONE
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-07-12T02:41:01-07:00
documentation
PROPIPE
is_lateral_inspection
false