Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2021, 08:51 AM
  • B 1144_B 1143_06182021_021157.mp4

Date
06/18/2021
W/O
896106
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01125
PipeID
P13446
Time
1:51 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8944
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_896106_TV16044_JUN2021
Sewer Type
Gravity
Material
BRICK
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 1144
Downstream MH
B 1143
Dir. of Survey
Downstream
Length Surveyed
629.4 ft.
Total Length
629.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2V00
O&M Rating
232
Overall Index
2
Overall Quick
Overall Rating
232
Pipe schematic from manhole B 1144 to B 1143
MH: B 1144MH: B 1143downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11440 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 35 %of cross sectional area49.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start87.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"165.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"235.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"276.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"279 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"326.5 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, #v, within 8 inches of joint: NO, 6", 3"331.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"331.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"379.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"379.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"430.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"430.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"477.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"528.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"528.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"575 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"575.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"626.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish629.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK629.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE629.4 ft. AMH - Downstream Manhole, Survey Ends - B 1143

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    49.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 12 o'clock, -, #v, within 8 inches of joint: NO, 6", 3"

    326.5 ft. - Tap Break-In Intruding, at 12 o'clock, -, #v, within 8 inches of joint: NO, 6", 3"

  • General Observation - COCKROACHES IN MANHOLE

    629.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (28)

DistanceCodeObservation
629.4MGOCONNECTION AT MH 9 O'CLOCK
430.2TFC
379.4TFA
131.3TFA
0MWL
629.4MGOCOCKROACHES IN MANHOLE
235.1TB
575.6TFC
379.4TFA
0AMHB 1144
49.9DAGS
276.5TBA
180.1TFC
0MGOCOCKROACHES IN MANHOLE
0MWM
430.2TFC
575TFC
87.1TFA
165.6TF
326.5TBI
477.3TFC
528.7TFA
279TFC
528.7TFC
331.1TFC
331.1TFC
629.4AMHB 1143
626.9DAGS

Properties (6)

additional_info
630069061721203
custom_field_two
3
customer
1
datetime
2021-06-18T01:51:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false