Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2021, 09:08 AM
  • B 1142_B 1141_06172021_022254.mp4

Date
06/17/2021
W/O
896106
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01125
PipeID
P13444
Time
2:08 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8941
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_896106_TV16044_JUN2021
Sewer Type
Gravity
Material
BRICK
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 1142
Downstream MH
B 1141
Dir. of Survey
Downstream
Length Surveyed
392.6 ft.
Total Length
392.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2O00
O&M Rating
156
Overall Index
2
Overall Quick
Overall Rating
156
Pipe schematic from manhole B 1142 to B 1141
MH: B 1142MH: B 1141downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11420 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start65.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"171.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"220.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"271.5 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6", 6"320.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"321.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"373.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"389.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish392.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK392.6 ft. AMH - Downstream Manhole, Survey Ends - B 1141392.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    392.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
321.8TFC
0MWM
389.8DAGS
220.3TBA
392.6MGOCONNECTION AT MH 3 O'CLOCK
0AMHB 1142
171.4TB
2DAGS
392.6AMHB 1141
373.8TFC
118.3TB
320.3TBA
0MGOCOCKROACHES IN MANHOLE
271.5TB
65.2TBA
392.6MGOCOCKROACHES IN MANHOLE
0MWL

Properties (7)

additional_info
630069061621201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-06-17T02:08:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false