Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 9, 2021, 04:43 AM
  • 02 1420_02 1419_06082021_214956.mp4

Date
06/08/2021
W/O
891419
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02991
Time
9:43 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8889
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_891419_TV02220_MAY2021
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
33 in.
Upstream MH
02 1420
Downstream MH
02 1419
Dir. of Survey
Downstream
Length Surveyed
40.3 ft.
Total Length
40.3 ft.
Structural Index
3
Structural Quick
5738
Structural Rating
73
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
73
Pipe schematic from manhole 02 1420 to 02 1419
MH: 02 1420MH: 02 1419downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14200 ft. MWM - Water Mark, 25 %of cross sectional area2.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"7.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start40.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES40.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish40.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish40.3 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.40.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    12.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

    40.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

    40.3 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

Observations (12)

DistanceCodeObservation
7.6TF
2.3SAP
40.3SRC
40.3SRV
40.3SSS
40.3MSAVIEW OF DOWNLEG OF U/S SIPHON.
12.2SRV
0MWL
0AMH02 1420
0MWM
7.6SSS
40.3SAP

Properties (7)

additional_info
630074060821202
custom_field_three
REINFORCEMENT CORRODED/AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-06-08T21:43:16-07:00
documentation
propipe
is_lateral_inspection
false