Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 10, 2021, 02:49 PM
  • 02 1407_02 1406_06102021_075625.mp4

Date
06/10/2021
W/O
891419
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00349
PipeID
P02978
Time
7:49 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8982
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_891419_TV02220_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
39 in.
Upstream MH
02 1407
Downstream MH
02 1406
Dir. of Survey
Downstream
Length Surveyed
188.6 ft.
Total Length
188.6 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
111
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
115
Pipe schematic from manhole 02 1407 to 02 1406
MH: 02 1407MH: 02 1406downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14070 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK2 ft. MGO - General Observation - MAG COAT4.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start188.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED188.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1406188.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
188.6MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
2MGOMAG COAT
188.6AMH02 1406
0AMH02 1407
0MWM
188.6SAP
0MWL
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MGOCONNECTION AT THE MH 3 OC'LOCK
4.1SAP

Properties (6)

custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-06-10T07:49:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false