Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2021, 06:56 AM
  • 02 1406_02 1405_06112021_001809.mp4

Date
06/10/2021
W/O
891419
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00349
PipeID
P02977
Time
11:56 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8937
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_891419_TV02220_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
39 in.
Upstream MH
02 1406
Downstream MH
02 1405
Dir. of Survey
Downstream
Length Surveyed
344.9 ft.
Total Length
344.9 ft.
Structural Index
4
Structural Quick
5M3M
Structural Rating
552
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
556
Pipe schematic from manhole 02 1406 to 02 1405
MH: 02 1406MH: 02 1405downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14060 ft. MWL - Water Level, 40 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start344.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish344.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1405344.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
344.9SAP
2SAP
0AMH02 1406
344.9AMH02 1405
0MWL
344.9SRV
2SRV

Properties (7)

additional_info
630069061021202
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-06-10T23:56:06-07:00
documentation
PRO PIPE
is_lateral_inspection
false