Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2021, 08:07 AM
  • 02 1401_02 1400_06112021_011336.mp4

Date
06/11/2021
W/O
891419
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00349
PipeID
P02972
Time
1:07 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8937
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_891419_TV02220_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
39 in.
Upstream MH
02 1401
Downstream MH
02 1400
Dir. of Survey
Downstream
Length Surveyed
163.1 ft.
Total Length
163.1 ft.
Structural Index
3
Structural Quick
5E3E
Structural Rating
312
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
312
Pipe schematic from manhole 02 1401 to 02 1400
MH: 02 1401MH: 02 1400downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 02 14010 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start157.5 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish157.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish160.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE160.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK160.5 ft. MGO - General Observation - STOP LOG CONNECTION AT MH 3 O'CLOCK163 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish163.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1400

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    160.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
2SRC
160.5MGOCOCKROACHES IN MANHOLE
157.5SRC
163SSS
2.1SSS
160.5MGOCONNECTION AT MH 9 O'CLOCK
160.5MGOSTOP LOG CONNECTION AT MH 3 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
157.5SAP
2SAP
163.1AMH02 1400
0AMH02 1401
0MWL
0MWM

Properties (6)

additional_info
630069061021202
custom_field_two
2
customer
1
datetime
2021-06-11T01:07:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false