Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 10, 2021, 11:07 AM
  • 02 1396_02 1395_06102021_043120.mp4

Date
06/10/2021
W/O
891419
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00349
PipeID
P02967
Time
4:07 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8894
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_891419_TV02220_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
39 in.
Upstream MH
02 1396
Downstream MH
02 1395
Dir. of Survey
Downstream
Length Surveyed
1001 ft.
Total Length
1001 ft.
Structural Index
4
Structural Quick
5g3g
Structural Rating
1592
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1592
Pipe schematic from manhole 02 1396 to 02 1395
MH: 02 1396MH: 02 1395downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13962 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING THROUGHOUT997.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish997.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1001 ft. AMH - Downstream Manhole, Survey Ends - 02 1395

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

Observations (9)

DistanceCodeObservation
1001AMH02 1395
0MWM
997.4SRV
0MWL
2SAP
2SRV
2MGOMAG COATING THROUGHOUT
997.4SAP
0AMH02 1396

Properties (7)

additional_info
630069060921201
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-06-10T04:07:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false