Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 10, 2021, 04:24 AM
  • 02 1391_02 1390_06092021_214425.mp4

Date
06/09/2021
W/O
891419
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00349
PipeID
P02962
Time
9:24 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8894
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_891419_TV02220_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
39 in.
Upstream MH
02 1391
Downstream MH
02 1390
Dir. of Survey
Downstream
Length Surveyed
287.1 ft.
Total Length
287.1 ft.
Structural Index
3
Structural Quick
5J3J
Structural Rating
570
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
570
Pipe schematic from manhole 02 1391 to 02 1390
MH: 02 1391MH: 02 1390downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13910 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start44.3 ft. MGO - General Observation - MAG COATING THROUGHOUT285.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish285.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish287 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish287.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1390

Observation photos (3)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    44.3 ft. - General Observation - MAG COATING THROUGHOUT

Observations (11)

DistanceCodeObservation
285.9SRV
287SSS
285.9SAP
0MWM
2SRV
0AMH02 1391
2.1SSS
0MWL
2SAP
287.1AMH02 1390
44.3MGOMAG COATING THROUGHOUT

Properties (7)

additional_info
630069060921201
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-06-09T21:24:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false