Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2021, 01:54 AM
  • A 0310_A 0309_07082021_193900.mp4

Date
07/08/2021
W/O
896129
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00325
PipeID
P08220
Time
6:54 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9067
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_896129_TV15003_JUN2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
21 in.
Upstream MH
A 0310
Downstream MH
A 0309
Dir. of Survey
Downstream
Length Surveyed
1068.8 ft.
Total Length
1068.8 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole A 0310 to A 0309
MH: A 0310MH: A 0309downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 03100 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT START150 ft. SAV - Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: NO - Moderate206 ft. SAV - Surface Aggregate Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - Moderate437.1 ft. SSS - Surface Spalling, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - Moderate443.1 ft. SSS - Surface Spalling, from 01 to 03 o'clock, within 8 inches of joint: NO, Finish - Moderate1066 ft. MGO - General Observation - MAG COAT END1068.8 ft. AMH - Downstream Manhole, Survey Ends - A 0309

Observations (10)

DistanceCodeObservation
0AMHA 0310
437.1SSSModerate
443.1SSSModerate
1066MGOMAG COAT END
206SAVModerate
150SAVModerate
2.1MGOMAG COAT START
1068.8AMHA 0309
0MWM
0MWL

Properties (8)

additional_info
630074070921061
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-07-08T18:54:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
28972