Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 2, 2017, 10:39 AM
  • Section#2_B 0929_B 0928__Date (SI_Date)__SI_Preset.mp4

Date
03/02/2017
W/O
0607740
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00333
PipeID
P20070
Time
2:39 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6770
Sewer Name
A JOINT OUTFALL A - UNIT 3B
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20170302MDM_JOINT_OUTFALL_A_UNIT_3B
Material
RCP-CTL
Shape
Square
Height
114 in.
Upstream MH
B 0929
Downstream MH
B 0928
Dir. of Survey
Downstream
Length Surveyed
23.4 ft.
Total Length
23.4 ft.
Structural Index
4
Structural Quick
5142
Structural Rating
13
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
17
Pipe schematic from manhole B 0929 to B 0928
MH: B 0929MH: B 0928downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:45AM0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - MH CONN 3:00 STOPLOG IN PLACE11.4 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG11.4 ft. MGO - General Observation - 100% MISSING TILES 10:00 TO 2:00 START17.9 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR23.1 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG23.1 ft. MGO - General Observation - 100% MISSING TILES 10:000 TO 2:00 FINISH23.4 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (3)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    11.4 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation -  100%  MISSING TILES 10:00 TO 2:00 START

    11.4 ft. - General Observation - 100% MISSING TILES 10:00 TO 2:00 START

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    17.9 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (10)

DistanceCodeObservation
11.4SAMSEVERE AGG
0AMH4:45AM
23.1SAMSEVERE AGG
0MWL
23.1MGO100% MISSING TILES 10:000 TO 2:00 FINISH
0MWM
23.4AMH5:00AM
17.9SRVCIRCUM REBAR
0MGOMH CONN 3:00 STOPLOG IN PLACE
11.4MGO100% MISSING TILES 10:00 TO 2:00 START

Properties (6)

custom_field_three
MISSING TILES ,MISSING SEVERE AGG ,1 CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2017-03-02T02:39:19-08:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false