Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2017, 09:06 AM
  • Section#1_18 1074_18 1073__Date (SI_Date)__SI_Preset.mp4

Date
03/01/2017
W/O
0624436
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00682
PipeID
P14933
Time
1:06 AM
Certificate
U115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6768
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 5
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
20170301VMR_AL_HABRA_HEIGHTS_TRUNK_SEC_5
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
18 1074
Downstream MH
18 1073
Dir. of Survey
Downstream
Length Surveyed
205.8 ft.
Total Length
205.8 ft.
Structural Index
1
Structural Quick
2418
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
1
Overall Quick
Overall Rating
16
Pipe schematic from manhole 18 1074 to 18 1073
MH: 18 1074MH: 18 1073downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. TFB - Tap Factory Made Abandoned, at 03 o'clock, -, within 8 inches of joint: NO, 4" - ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 12:57 AM0 ft. MWM - Water Mark, 10 %of cross sectional area4.9 ft. JOM - Joint Offset Medium8.8 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES13 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES18.1 ft. JOM - Joint Offset Medium20.1 ft. JOL - Joint Offset Large35.6 ft. CC - Crack Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES47.7 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES56.7 ft. CC - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES79.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - OPEN83.7 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES89.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES198.4 ft. CC - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES203.3 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES205.8 ft. AMH - Downstream Manhole, Survey Ends - 01:25AM

Observation photos (2)

  • Joint Offset Medium

    18.1 ft. - Joint Offset Medium

  • Joint Offset Large

    20.1 ft. - Joint Offset Large

Observations (18)

DistanceCodeObservation
56.7CC
0MWL
0TFBACTIVE
203.3CC
83.7CL
198.4CC
13CC
8.8CC
0AMH12:57 AM
4.9JOM
89.7CL
35.6CC
79.3TFOPEN
0MWM
47.7CL
18.1JOM
20.1JOL
205.8AMH01:25AM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2017-03-01T01:06:56-08:00
documentation
REVELES, MANANES, OLIVER III
is_lateral_inspection
false