Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2017, 05:56 PM
  • 18 0996_18 0995_312017_102201.mp4

Date
03/01/2017
W/O
0618956
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00677
PipeID
P14850
Time
9:56 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7346
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 1
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20170301DF_LA_HABRA_HEIGHTS_TRUNK_SEC_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
18 0996
Downstream MH
18 0995
Dir. of Survey
Downstream
Length Surveyed
60.3 ft.
Total Length
60.3 ft.
Structural Index
3
Structural Quick
5334
Structural Rating
30
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
30
Pipe schematic from manhole 18 0996 to 18 0995
MH: 18 0996MH: 18 0995downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:25 AM0 ft. MWL - Water Level, 20 %of cross sectional area0.1 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open8.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"13.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES16.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES22.4 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES28.3 ft. B - Broken, from 07 to 11 o'clock, within 8 inches of joint: YES31.7 ft. CM - Crack Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES41.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open46.2 ft. B - Broken, from 03 to 10 o'clock, within 8 inches of joint: YES52.3 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES52.3 ft. JOM - Joint Offset Medium - 6 TO 10 O'CLOCK53.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"57.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish60.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active60.3 ft. AMH - Downstream Manhole, Survey Ends - 10:47 AM

Observation photos (9)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    13.2 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    16.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    22.4 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 11 o'clock, within 8 inches of joint: YES

    28.3 ft. - Broken, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES

    31.7 ft. - Crack Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES

  • Broken, from 03 to 10 o'clock, within 8 inches of joint: YES

    46.2 ft. - Broken, from 03 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    52.3 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium - 6 TO 10 O'CLOCK

    52.3 ft. - Joint Offset Medium - 6 TO 10 O'CLOCK

Observations (19)

DistanceCodeObservation
8.1TFOpen
41.5TFOpen
2SSS
46.2B
0.1MWM
16.5CM
60.3MGOConn. @ Mh, 9 O' Clock. Active
52.3CM
0AMH10:25 AM
31.7CM
53.2TFC
28.3B
57.7SSS
60.3AMH10:47 AM
13.2FL
52.3JOM6 TO 10 O'CLOCK
0MWL
22.4B
8.4TFC

Properties (6)

custom_field_three
BROKEN PIPE
custom_field_two
2
customer
LACSD
datetime
2017-03-01T09:56:46-08:00
documentation
FRANKLIN, BRAR
is_lateral_inspection
false