Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2016, 08:18 AM
  • A 0308_A 0307_2112016_011245.mp4

Date
02/11/2016
W/O
0556813
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08218
Time
12:18 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0049
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
20160211MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
A 0308
Downstream MH
A 0307
Dir. of Survey
Downstream
Length Surveyed
18.9 ft.
Total Length
18.9 ft.
Structural Index
4
Structural Quick
5141
Structural Rating
11
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
16
Pipe schematic from manhole A 0308 to A 0307
MH: A 0308MH: A 0307downstream0 ft. MWL - Water Level, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:30AM0 ft. MWM - Water Mark, 80 %of cross sectional area2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE12.4 ft. MGO - General Observation - HANGING MASTIC AT JOINT12.4 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish12.4 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG14.1 ft. MGO - General Observation - PEELING MASTIC AT JOINT15.9 ft. SRC - Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR17.5 ft. MGO - General Observation - HANGING MASTIC17.6 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish18.6 ft. SRC - Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: YES, Finish18.9 ft. MSA - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observation photos (8)

  • Water Level, 80 %of cross sectional area

    0 ft. - Water Level, 80 %of cross sectional area

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - HANGING MASTIC AT JOINT

    12.4 ft. - General Observation - HANGING MASTIC AT JOINT

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    12.4 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - PEELING MASTIC AT JOINT

    14.1 ft. - General Observation - PEELING MASTIC AT JOINT

  • Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    15.9 ft. - Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • General Observation - HANGING MASTIC

    17.5 ft. - General Observation - HANGING MASTIC

  • Survey Abandoned - DOWNLEG UPSTREAM SIPHON

    18.9 ft. - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observations (13)

DistanceCodeObservation
18.9MSADOWNLEG UPSTREAM SIPHON
17.5MGOHANGING MASTIC
2SSSBLISTERING PEELING CONCRETE
14.1MGOPEELING MASTIC AT JOINT
12.4MGOHANGING MASTIC AT JOINT
18.6SRC
0MWL
0AMH12:30AM
12.4SSS
12.4SAMSEVERE AGG
15.9SRCCIRCUM REBAR
0MWM
17.6SAM

Properties (8)

additional_info
DOWNLEG UPSTREAM SIPHON
custom_field_three
CORRODED REBAR CIRCUM
custom_field_two
1
customer
LACSD
datetime
2016-02-11T00:18:14-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false
year_laid
19790427