Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2016, 08:42 AM
  • 05 2208_05 2203_252016_011219.mp4

Date
02/05/2016
W/O
0536424
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00509
PipeID
P07349
Time
12:42 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0042
Sewer Name
05 PRAIRIE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
20160205MDM_PRAIRIE_AVENUE_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 2208
Downstream MH
05 2203
Dir. of Survey
Downstream
Length Surveyed
24.6 ft.
Total Length
24.6 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 05 2208 to 05 2203
MH: 05 2208MH: 05 2203downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM0 ft. MGO - General Observation - MH CONNACTIVE 6:000 ft. MGO - General Observation - MH CONN OPEN 9:002 ft. MSC - Shape or Size Change, -, 12" - PIPE APPEARS 12"VCP START2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT2 ft. MSC - Shape or Size Change, -, 12" - 12" VCP6 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start15 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start15 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish24.2 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish24.2 ft. MSC - Shape or Size Change, -, 12" - 12" VCP FINISH24.6 ft. AMH - Downstream Manhole, Survey Ends - 1:10AM

Observation photos (6)

  • Shape or Size Change, -, 12" - PIPE APPEARS 12"VCP START

    2 ft. - Shape or Size Change, -, 12" - PIPE APPEARS 12"VCP START

  • Shape or Size Change, -, 12" - 12" VCP

    2 ft. - Shape or Size Change, -, 12" - 12" VCP

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    6 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 20 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    15 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Shape or Size Change, -, 12" - 12" VCP FINISH

    24.2 ft. - Shape or Size Change, -, 12" - 12" VCP FINISH

  • Downstream Manhole, Survey Ends - 1:10AM

    24.6 ft. - Downstream Manhole, Survey Ends - 1:10AM

Observations (12)

DistanceCodeObservation
24.2DAGS
24.6AMH1:10AM
15DAGS
0AMH12:45AM
2MSCPIPE APPEARS 12"VCP START
2FCSLIGHT
2MSC12" VCP
15DAGS
6DAGS
0MGOMH CONNACTIVE 6:00
0MGOMH CONN OPEN 9:00
24.2MSC12" VCP FINISH

Properties (7)

custom_field_three
12" VCP 1 SLIGHT FRACTURE
custom_field_two
4
customer
LACSD
datetime
2016-02-05T00:42:36-08:00
documentation
MARTIN,MANANES
is_lateral_inspection
false
year_laid
19721005