Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2016, 06:20 PM
  • A 0644_A 0643_242016_103003.mp4

Date
02/04/2016
W/O
0536342
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00316
PipeID
P07851
Time
10:20 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7045
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
34
Purpose
Capital Improvement Program Assesment
Project
20160204AM_JOA_1A_DISTRICT_21_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
A 0644
Downstream MH
A 0643
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole A 0644 to A 0643
MH: A 0644MH: A 0643downstream0 ft. MGO - General Observation - AIRLINE0 ft. AMH - Upstream Manhole, Survey Begins - 10:30 AM0 ft. MWL - Water Level, 100 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO2.1 ft. MSA - Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observation photos (5)

  • General Observation - AIRLINE

    0 ft. - General Observation - AIRLINE

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

  • Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

    2.1 ft. - Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observations (7)

DistanceCodeObservation
0MGOAIRLINE
2.1MSAVIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
2SAV
0AMH10:30 AM
2SSS
0MWL
2SRV

Properties (7)

additional_info
RFIR INSPECTION, VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
custom_field_three
SEV. EXP. AGG, SPALLING, AND REBAR
custom_field_two
2
customer
LACSD
datetime
2016-02-04T10:20:56-08:00
documentation
MIRANDA, SHADLER, MIRABAL
is_lateral_inspection
false