Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2021, 09:41 AM
  • C 0211_C 0210_7132021_024354.mp4

Date
07/13/2021
W/O
0896123
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09603
Time
2:41 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1870
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20210713MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0211
Downstream MH
C 0210
Dir. of Survey
Downstream
Length Surveyed
287.8 ft.
Total Length
287.8 ft.
Structural Index
2
Structural Quick
2400
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole C 0211 to C 0210
MH: C 0211MH: C 0210downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:45AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - MAG COAT 95% START36.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE59.2 ft. MGO - General Observation - 98% MAG COAT173.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE278.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO287.1 ft. MGO - General Observation - 95% MAG COAT FINISH287.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE287.8 ft. AMH - Downstream Manhole, Survey Ends - 3:05AM

Observation photos (6)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - MAG COAT 95% START

    2 ft. - General Observation - MAG COAT 95% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    36.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • General Observation - 98% MAG COAT

    59.2 ft. - General Observation - 98% MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    173.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

    278.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

Observations (12)

DistanceCodeObservation
287.8AMH3:05AM
287.1MGO95% MAG COAT FINISH
36.6SSSBLISTERING PEELING CONCRETE
0AMH2:45AM
287.1SSSBLISTERING PEELING CONCRETE
278.7SSS
0MWL
0MWM
2SSSBLISTTERING PEELING CONCRETE UNDER MAG COAT
2MGOMAG COAT 95% START
173.8SSSBLISTERING PEELING CONCRETE
59.2MGO98% MAG COAT

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE- 95% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2021-07-13T02:41:57-07:00
documentation
MARTIN,OLIVER 111,BARR,RAMIERZ
is_lateral_inspection
false