Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2021, 07:12 AM
  • C 0212_C 0211_7132021_015452.mp4

Date
07/13/2021
W/O
0896123
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09604
Time
12:12 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1870
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20210713MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0212
Downstream MH
C 0211
Dir. of Survey
Downstream
Length Surveyed
408.9 ft.
Total Length
408.9 ft.
Structural Index
2
Structural Quick
2500
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole C 0212 to C 0211
MH: C 0212MH: C 0211downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - MAG COAT 95% START52.3 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE104.1 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE224.2 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE302 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE408 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE408 ft. MGO - General Observation - 95% MAG COAT FINISH408.9 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM

Observation photos (6)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - MAG COAT 95% START

    2 ft. - General Observation - MAG COAT 95% START

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    52.3 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    104.1 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    224.2 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    302 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

Observations (12)

DistanceCodeObservation
52.3SSSBLISTERING PEELING CONCRETE
408.9AMH2:30AM
408SSSBLISTERING PEELING CONCRETE
0MWM
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
302SSSBLISTERING PEELING CONCRETE
224.2SSSPEELING CONCRETE
408MGO95% MAG COAT FINISH
0MWL
0AMH1:55AM
104.1SSSBLISTERING PEELING CONCRETE
2MGOMAG COAT 95% START

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE- 985 MAG COAT
custom_field_two
3
customer
LACSD
datetime
2021-07-13T00:12:30-07:00
documentation
MARTIN,OLIVER 111,BARR,RAMIERZ
is_lateral_inspection
false