Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2021, 07:28 AM
  • B 0451_B 0450_06182021_003645.mp4

Date
06/18/2021
W/O
896722
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00093
PipeID
P08963
Time
12:28 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8943
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_896722_TV16034_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
57 in.
Upstream MH
B 0451
Downstream MH
B 0450
Dir. of Survey
Downstream
Length Surveyed
173.2 ft.
Total Length
173.2 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
102
O&M Index
2
O&M Quick
412F
O&M Rating
72
Overall Index
3
Overall Quick
Overall Rating
174
Pipe schematic from manhole B 0451 to B 0450
MH: B 0451MH: B 0450downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04510 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start78.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"78.7 ft. RBL - Roots Ball Lateral, from 06 to 12 o'clock, 55 %, within 8 inches of joint: YES83.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"151.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"170.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish170.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish173.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE173.2 ft. AMH - Downstream Manhole, Survey Ends - B 0450

Observation photos (5)

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Ball Lateral, from 06 to 12 o'clock, 55 %, within 8 inches of joint: YES

    78.7 ft. - Roots Ball Lateral, from 06 to 12 o'clock, 55 %, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    173.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
173.2MGOCOCKROACHES IN MANHOLE
2MGOMAG COATING THROUGHOUT
0MWL
78.7TFA
170.6DAGS
173.2AMHB 0450
78.7RBL
2DAGS
0AMHB 0451
2SAP
83.9TFC
151.2TFA
170.6SAP
0MWM

Properties (7)

additional_info
630069061721202
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-06-18T00:28:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false