Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2021, 07:37 AM
  • B 0450_B 0449_06182021_004743.mp4

Date
06/18/2021
W/O
896722
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00093
PipeID
P08962
Time
12:37 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8943
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_896722_TV16034_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
63 in.
Upstream MH
B 0450
Downstream MH
B 0449
Dir. of Survey
Downstream
Length Surveyed
229.6 ft.
Total Length
229.6 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
135
O&M Index
2
O&M Quick
2H00
O&M Rating
90
Overall Index
3
Overall Quick
Overall Rating
225
Pipe schematic from manhole B 0450 to B 0449
MH: B 0450MH: B 0449downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04500 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start19.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"58.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"62.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"122 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"184.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish227.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish229.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK229.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE229.6 ft. AMH - Downstream Manhole, Survey Ends - B 0449

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    19.5 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - COCKROACHES IN MANHOLE

    229.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
184.4TFC
58.9TFC
229.6MGOCONNECTION AT MH 9 O'CLOCK
227.7DAGS
124.7TFC
122TFA
0MWM
227.7SAP
62.2TFA
229.6MGOCOCKROACHES IN MANHOLE
2SAP
2DAGS
0AMHB 0450
19.5TFA
0MWL
0MGOCOCKROACHES IN MANHOLE
229.6AMHB 0449
187.1TFA

Properties (7)

additional_info
630069061721202
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-06-18T00:37:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false