Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2021, 09:35 AM
  • B 0442_B 0441_06222021_024936.mp4

Date
06/22/2021
W/O
896722
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00093
PipeID
P08954
Time
2:35 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8950
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_896722_TV16034_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
63 in.
Upstream MH
B 0442
Downstream MH
B 0441
Dir. of Survey
Downstream
Length Surveyed
392.5 ft.
Total Length
392.5 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
234
O&M Index
2
O&M Quick
4131
O&M Rating
165
Overall Index
2
Overall Quick
Overall Rating
399
Pipe schematic from manhole B 0442 to B 0441
MH: B 0442MH: B 0441downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04422 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start205.3 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR220.2 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR234.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"283.9 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR319.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"389.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish389.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish392.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE392.5 ft. AMH - Downstream Manhole, Survey Ends - B 0441392.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

    205.3 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

  • Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR

    220.2 ft. - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

    283.9 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

  • General Observation - COCKROACHES IN MANHOLE

    392.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
319.3TBA
392.5MGOCOCKROACHES IN MANHOLE
389.8SAP
234.2TBA
392.5AMHB 0441
389.8DAGS
283.9RFJ
205.3RFJ
220.2RMJ
2DAGS
0MWL
0MWM
2SAP
0AMHB 0442
392.5MGOCONNECTION AT MH 9 O'CLOCK

Properties (7)

additional_info
630069062121203
custom_field_three
PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-06-22T02:35:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false