Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2021, 10:37 AM
  • 15 0709_15 0708_06112021_034942.mp4

Date
06/11/2021
W/O
896391
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12601
Time
3:37 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8984
Sewer Name
15 EL MONTE AVENUE TRUNK
City
ARCADIA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
WO_896391_TV15081_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0708
Downstream MH
15 0709
Dir. of Survey
Upstream
Length Surveyed
283.7 ft.
Total Length
283.7 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 15 0708 to 15 0709
MH: 15 0708MH: 15 0709upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 07093.2 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES25.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES176.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES262.8 ft. CS - Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES277.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES283.7 ft. MWL - Water Level, 20 %of cross sectional area283.7 ft. AMH - Downstream Manhole, Survey Begins - 15 0708283.7 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (5)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    5.8 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

    20.9 ft. - Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    107.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    258.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    280.5 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
0MWL
5.8CL
0AMH15 0708
20.9CS
0MWM
283.7AMH15 0709
280.5B
258.5CM
107.3CM

Properties (6)

custom_field_three
MULTIPLE CRACKS, BROKEN
custom_field_two
2
customer
1
datetime
2021-06-11T03:37:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false