Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2021, 10:14 AM
  • 15 0707_15 0706_06112021_032537.mp4

Date
06/11/2021
W/O
896391
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12599
Time
3:14 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8984
Sewer Name
15 EL MONTE AVENUE TRUNK
City
ARCADIA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
WO_896391_TV15081_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0706
Downstream MH
15 0707
Dir. of Survey
Upstream
Length Surveyed
323 ft.
Total Length
323 ft.
Structural Index
2
Structural Quick
2400
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 15 0706 to 15 0707
MH: 15 0706MH: 15 0707upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 070723.5 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES88.7 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES204.9 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES245.7 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES323 ft. MWM - Water Mark, 40 %of cross sectional area323 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK323 ft. AMH - Downstream Manhole, Survey Begins - 15 0706323 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (4)

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    77.3 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    118.1 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    234.3 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    299.5 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
77.3CS
323AMH15 0707
0MWM
118.1CS
0MGOCONNECTION AT THE MH 9 OC'LOCK
299.5CS
234.3CS
0AMH15 0706
0MWL

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-11T03:14:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false