Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2021, 09:25 AM
  • 15 0706_15 0705_06112021_023741.mp4

Date
06/11/2021
W/O
896391
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12598
Time
2:25 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8984
Sewer Name
15 EL MONTE AVENUE TRUNK
City
ARCADIA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
WO_896391_TV15081_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0706
Downstream MH
15 0705
Dir. of Survey
Downstream
Length Surveyed
333 ft.
Total Length
333 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
2
O&M Quick
332L
O&M Rating
141
Overall Index
3
Overall Quick
Overall Rating
336
Pipe schematic from manhole 15 0706 to 15 0705
MH: 15 0706MH: 15 0705downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 07060 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start209.5 ft. RMC - Roots Medium Connection, from 01 to 03 o'clock, 15 %, within 8 inches of joint: YES210.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"228.1 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR249.3 ft. RMJ - Roots Medium Joint, from 04 to 05 o'clock, 5 %, within 8 inches of joint: YESR333 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish333 ft. AMH - Downstream Manhole, Survey Ends - 15 0705333 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 01 to 03 o'clock, 15 %, within 8 inches of joint: YES

    209.5 ft. - Roots Medium Connection, from 01 to 03 o'clock, 15 %, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    210.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

    228.1 ft. - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 04 to 05 o'clock, 5 %, within 8 inches of joint: YESR

    249.3 ft. - Roots Medium Joint, from 04 to 05 o'clock, 5 %, within 8 inches of joint: YESR

Observations (13)

DistanceCodeObservation
2.1DAGS
0AMH15 0706
333DAGS
249.3RMJ
0MWL
210.4TB
228.1RMJ
7.1CM
333AMH15 0705
0MGOCONNECTION AT THE MH 3 OC'LOCK
209.5RMC
0MWM
333CM

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-11T02:25:20-07:00
documentation
PRO PIPE
is_lateral_inspection