Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2021, 09:38 AM
  • 15 0705_15 0704_06112021_025028.mp4

Date
06/11/2021
W/O
896391
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12597
Time
2:38 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8984
Sewer Name
15 EL MONTE AVENUE TRUNK
City
ARCADIA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
WO_896391_TV15081_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0705
Downstream MH
15 0704
Dir. of Survey
Downstream
Length Surveyed
327.5 ft.
Total Length
327.5 ft.
Structural Index
3
Structural Quick
3H21
Structural Rating
143
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
273
Pipe schematic from manhole 15 0705 to 15 0704
MH: 15 0705MH: 15 0704downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07052.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start15.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES56 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES96.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start327.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK327.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0704327.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish327.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    15.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    56 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    96.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
56CM
327.5MGOCONNECTION AT THE MH 3 OC'LOCK
96.1CM
327.5AMH15 0704
15.8CL
327.5CM
0MWM
0AMH15 0705
2.8DAGS
327.5DAGS

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-11T02:38:52-07:00
documentation
PRO PIPE
is_lateral_inspection
false