Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 14, 2021, 09:45 AM
  • 15 0699_15 0698_06142021_025848.mp4

Date
06/14/2021
W/O
896391
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12591
Time
2:45 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8985
Sewer Name
15 EL MONTE AVENUE TRUNK
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
WO_896391_TV15081_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0699
Downstream MH
15 0698
Dir. of Survey
Downstream
Length Surveyed
250.1 ft.
Total Length
250.1 ft.
Structural Index
3
Structural Quick
3H21
Structural Rating
143
O&M Index
2
O&M Quick
2I12
O&M Rating
102
Overall Index
2
Overall Quick
Overall Rating
245
Pipe schematic from manhole 15 0699 to 15 0698
MH: 15 0699MH: 15 0698downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06990 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.5 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES13.1 ft. CM - Crack Multiple, from 07 to 08 o'clock, within 8 inches of joint: YES20.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start119 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"119 ft. RFL - Roots Fine Lateral, from 06 to 09 o'clock120.8 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: YES, 6"120.8 ft. RFL - Roots Fine Lateral, from 12 to 12 o'clock142.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"207.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"250.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish250.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish250.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0698

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    4.5 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 08 o'clock, within 8 inches of joint: YES

    13.1 ft. - Crack Multiple, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Lateral, from 06 to 09 o'clock

    119 ft. - Roots Fine Lateral, from 06 to 09 o'clock

  • Tap Break-In, at 09 o'clock, -, within 8 inches of joint: YES, 6"

    120.8 ft. - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: YES, 6"

  • Roots Fine Lateral, from 12 to 12 o'clock

    120.8 ft. - Roots Fine Lateral, from 12 to 12 o'clock

Observations (18)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
120.8TB
142.7TFC
0MWL
120.8RFL
20.7CM
250.1CM
250.1DAGS
119TF
0MWM
250.1AMH15 0698
207.8TFC
0AMH15 0699
4.5CL
0MGOCONNECTION AT MH 3 O'CLOCK
13.1CM
2.6DAGS
119RFL

Properties (6)

custom_field_three
multiple cracks
custom_field_two
3
customer
1
datetime
2021-06-14T02:45:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false