Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2021, 08:34 AM
  • 15 0692_15 0691_06212021_014726.mp4

Date
06/21/2021
W/O
896391
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12584
Time
1:34 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8989
Sewer Name
15 EL MONTE AVENUE TRUNK
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
WO_896391_TV15081_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0692
Downstream MH
15 0691
Dir. of Survey
Downstream
Length Surveyed
266.1 ft.
Total Length
266.1 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
1
O&M Quick
2112
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 15 0692 to 15 0691
MH: 15 0692MH: 15 0691downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06922.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.9 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES12.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"89.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"89.9 ft. RFL - Roots Fine Lateral, from 12 to 12 o'clock101.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"147.7 ft. FS - Fracture Spiral, from 03 to 06 o'clock, within 8 inches of joint: YES149 ft. RFL - Roots Fine Lateral, from 03 to 08 o'clock149 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"263.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish263.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish266.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0691266.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK266.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    8.9 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Lateral, from 12 to 12 o'clock

    89.9 ft. - Roots Fine Lateral, from 12 to 12 o'clock

  • Fracture Spiral, from 03 to 06 o'clock, within 8 inches of joint: YES

    147.7 ft. - Fracture Spiral, from 03 to 06 o'clock, within 8 inches of joint: YES

  • Roots Fine Lateral, from 03 to 08 o'clock

    149 ft. - Roots Fine Lateral, from 03 to 08 o'clock

Observations (18)

DistanceCodeObservation
0MWM
266.1AMH15 0691
89.9TF
2.3DAGS
266.1MGOCONNECTION AT MH 9 O'CLOCK
38.7TFC
263.8CM
8.9CM
266.1MGOCONNECTION AT MH 3 O'CLOCK
147.7FS
0MWL
12.6CM
89.9RFL
101.2TFC
0AMH15 0692
263.8DAGS
149RFL
149TF

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-21T01:34:12-07:00
documentation
PRO PIPE
is_lateral_inspection
false