Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2021, 07:57 AM
  • 15 0683_15 0682_06222021_010539.mp4

Date
06/22/2021
W/O
896391
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00602
PipeID
P12575
Time
12:57 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8990
Sewer Name
15 EL MONTE AVENUE TRUNK
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_896391_TV15081_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0683
Downstream MH
15 0682
Dir. of Survey
Downstream
Length Surveyed
27.3 ft.
Total Length
27.3 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole 15 0683 to 15 0682
MH: 15 0683MH: 15 0682downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 OCOCK0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06830 ft. MWL - Water Level, 20 %of cross sectional area2.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES12.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES25.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish27.3 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK27.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0682

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    12.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
3.8CM
27.3MGOCONNECTION AT MH 3 OCLOCK
0MGOCONNECTION AT MH 9 OCOCK
25.7DAGS
2.3TFDEBRIS
12.3CM
27.3AMH15 0682
0MWM
2.3DAGS
0AMH15 0683
0MWL

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-06-22T00:57:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false