Wastewater/Activity/PacpInspection/1.0Jun 30, 2021, 06:40 AM
  • J 0407_J 0194_06292021_235350.mp4

Date
06/29/2021
W/O
896126
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00055
PipeID
P11434
Time
11:40 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9062
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
RANCHO PALOS VERDES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
48
Purpose
Routine Assessment
Project
RFIR_WO_896126_TV05367_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
J 0407
Downstream MH
J 0194
Dir. of Survey
Downstream
Length Surveyed
357.2 ft.
Total Length
357.2 ft.
Structural Index
4
Structural Quick
4E31
Structural Rating
119
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
3
Overall Quick
Overall Rating
233
Pipe schematic from manhole J 0407 to J 0194
MH: J 0407MH: J 0194downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 040771.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start203.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES213.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start357.2 ft. AMH - Downstream Manhole, Survey Ends - J 0194357.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish357.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    71.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    203.1 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    213.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
203.1FL
71.3DAGS
357.2AMHJ 0194
0MWL
213.5FM
0AMHJ 0407
357.2FM
357.2DAGS

Properties (7)

additional_info
630074062921201
custom_field_three
CRACKS/ FRACTURE'S
custom_field_two
3
customer
1
datetime
2021-06-29T23:40:04-07:00
documentation
PROPIPE
is_lateral_inspection
false