Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 30, 2021, 08:02 AM
  • J 0191_J 0190_06302021_012010.mp4

Date
06/30/2021
W/O
896545
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00055
PipeID
P11430
Time
1:02 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9063
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
SAN PEDRO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47A
Purpose
Routine Assessment
Project
RFIR_WO_896545_TV05380_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
J 0191
Downstream MH
J 0190
Dir. of Survey
Downstream
Length Surveyed
595.7 ft.
Total Length
595.7 ft.
Structural Index
3
Structural Quick
483B
Structural Rating
78
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
78
Pipe schematic from manhole J 0191 to J 0190
MH: J 0191MH: J 0190downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 0191376.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES380.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start421.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish488.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES493.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES523.8 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES533.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start593.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish595.7 ft. AMH - Downstream Manhole, Survey Ends - J 0190

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    376.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    380.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    493.9 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    523.8 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    533.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
533.5CM
0MWM
0AMHJ 0191
493.9FL
421.7FM
376.3CM
595.7AMHJ 0190
523.8CL
380.8FM
488.5CL
593.9CM

Properties (6)

custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-06-30T01:02:43-07:00
documentation
PROPIPE
is_lateral_inspection
false