Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2021, 07:22 AM
  • 19 0214_19 0213_06242021_003441.mp4

Date
06/24/2021
W/O
896576
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00718
PipeID
P15183
Time
12:22 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9005
Sewer Name
19 ARTESIA-CERRITOS TRUNK
City
ARTESIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_896576_TV19059_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
19 0214
Downstream MH
19 0213
Dir. of Survey
Downstream
Length Surveyed
265.2 ft.
Total Length
265.2 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
129
O&M Index
2
O&M Quick
412T
O&M Rating
212
Overall Index
2
Overall Quick
Overall Rating
341
Pipe schematic from manhole 19 0214 to 19 0213
MH: 19 0214MH: 19 0213downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 19 02142 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start18.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"48.6 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES52.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start78.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"89.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"130.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"184.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"194.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"229.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"262.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish262.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish262.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish265.2 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK265.2 ft. AMH - Downstream Manhole, Survey Ends - 19 0213265.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    48.6 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    52.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    265.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (23)

DistanceCodeObservation
0MWM
229.8TFC
78.3TF
2DAGS
52.6CM
194.9TFA
0MGOCONNECTION AT MH 9 O'CLOCK
18.7TFC
140.6TFA
2DAE
0MWL
107.9TF
262.7CM
0AMH19 0214
265.2MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
89.4TF
262.7DAGS
48.6CM
265.2AMH19 0213
130.2TFC
184.2TF
265.2MGOCOCKROACHES IN MANHOLE
262.7DAE

Properties (7)

additional_info
630069062321203
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2021-06-24T00:22:41-07:00
documentation
PRO PIPE
is_lateral_inspection
false