- Date
- 06/22/2021
- W/O
- 896401
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00242
- PipeID
- P03906
- Time
- 9:42 PM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9001
- Sewer Name
- 02 CLOVERLAWN TRUNK
- City
- PARAMOUNT
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 31
- Purpose
- Routine Assessment
- Project
- WO_896401_TV02041_JUN2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Width
- 24 in.
- Upstream MH
- 02 1388
- Downstream MH
- 02 1387
- Dir. of Survey
- Downstream
- Length Surveyed
- 355 ft.
- Total Length
- 355 ft.
- Structural Index
- 3
- Structural Quick
- 3H22
- Structural Rating
- 143
- O&M Index
- 2
- O&M Quick
- 2M00
- O&M Rating
- 140
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 283
Pipe schematic from manhole 02 1388 to 02 1387 Observation photos (7)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

4.2 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

8.3 ft. - Joint Offset Medium

87.9 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

121.7 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

128 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

354.9 ft. - General Observation - COCKROACHES IN MANHOLE