Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2021, 10:58 AM
  • 32 0081A_32 0081_07062021_041500.mp4

Date
07/06/2021
W/O
896103
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00889
PipeID
P19845
Time
3:58 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9021
Sewer Name
32 RYE CANYON TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
06
Purpose
Routine Assessment
Project
WO_896103_TV32020_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
32 0081A
Downstream MH
32 0081
Dir. of Survey
Downstream
Length Surveyed
373.1 ft.
Total Length
373.1 ft.
Structural Index
3
Structural Quick
3421
Structural Rating
14
O&M Index
2
O&M Quick
2N00
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
162
Pipe schematic from manhole 32 0081A to 32 0081
MH: 32 0081AMH: 32 0081downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 32 0081A2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start75.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"140.1 ft. MGO - General Observation - DATA STATES RCP.179 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES180.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"196.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start216 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish366.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES371.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish373.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE373.1 ft. AMH - Downstream Manhole, Survey Ends - 32 0081

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    196.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    366.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    373.1 ft. - General Observation - COCKROACHES IN MANHOLE

  • Downstream Manhole, Survey Ends - 32 0081

    373.1 ft. - Downstream Manhole, Survey Ends - 32 0081

Observations (16)

DistanceCodeObservation
373.1MGOCOCKROACHES IN MANHOLE
371.2DAGS
180.7TFA
2DAGS
0MWM
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
0MGOCOCKROACHES IN MANHOLE
366.3CM
75.3TFA
196.4CM
179CL
216CM
140.1MGODATA STATES RCP.
0AMH32 0081A
373.1AMH32 0081

Properties (7)

additional_info
630069070621001
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-07-06T03:58:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false