Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2021, 09:18 AM
  • 32 0079_32 0078_07062021_023216.mp4

Date
07/06/2021
W/O
896103
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00889
PipeID
P19842
Time
2:18 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9021
Sewer Name
32 RYE CANYON TRUNK
City
VALENCIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
06
Purpose
Routine Assessment
Project
WO_896103_TV32020_JUN2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
32 0078
Downstream MH
32 0079
Dir. of Survey
Upstream
Length Surveyed
483.4 ft.
Total Length
483.4 ft.
Structural Index
3
Structural Quick
3R2M
Structural Rating
421
O&M Index
2
O&M Quick
2R00
O&M Rating
192
Overall Index
2
Overall Quick
Overall Rating
613
Pipe schematic from manhole 32 0078 to 32 0079
MH: 32 0078MH: 32 0079upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 32 00790 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK1.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish283.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"341.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start477.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start481.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start483.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE483.4 ft. AMH - Downstream Manhole, Survey Begins - 32 0078483.4 ft. MWL - Water Level, 10 %of cross sectional area483.4 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    141.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    483.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
481.6SSS
199.6TBA
0AMH32 0078
483.4MGOCOCKROACHES IN MANHOLE
0MWL
141.8SSS
483.4AMH32 0079
0MWM
481.6SAV
483.4MGOCONNECTION AT MH 9 O'CLOCK
2DAGS
481.6DAGS
5.8SAV

Properties (7)

additional_info
630069070621001
custom_field_three
SPALLING/VISIBLE AGGREGATE
custom_field_two
2
customer
1
datetime
2021-07-06T02:18:20-07:00
documentation
PRO PIPE
is_lateral_inspection
false