Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 7, 2021, 06:32 AM
  • 20 0211_20 0210_07062021_235226.mp4

Date
07/06/2021
W/O
896099
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00750
PipeID
P19178
Time
11:32 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9022
Sewer Name
20 20TH STREET EAST TRUNK
City
PALMDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
07
Purpose
Routine Assessment
Project
WO_896099_TV20003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
20 0211
Downstream MH
20 0210
Dir. of Survey
Downstream
Length Surveyed
302.5 ft.
Total Length
302.5 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
3
Overall Quick
Overall Rating
297
Pipe schematic from manhole 20 0211 to 20 0210
MH: 20 0211MH: 20 0210downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 20 02112 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"16.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"59.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"63.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"114.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"116.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"159.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"162.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"214.2 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"217.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"260 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"263.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"300.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish300.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish302.5 ft. AMH - Downstream Manhole, Survey Ends - 20 0210302.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    302.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
2DAGS
116.5TFC
0MGOCONNECTION AT MH 9 O'CLOCK
217.3TFC
59.7TFC
260TFC
0MWM
162.8TFC
302.5AMH20 0210
6CM
300.1DAGS
263.3TFC
16.6TFC
63.1TFC
0MWL
114.1TFC
159.5TFC
13.2TFC
0AMH20 0211
302.5MGOCOCKROACHES IN MANHOLE
214.2TFC
300.1CM

Properties (7)

additional_info
630069070621201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-07-06T23:32:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false