Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2021, 05:36 AM
  • 20 0208_20 0207_07072021_225230.mp4

Date
07/07/2021
W/O
896099
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00750
PipeID
P19175
Time
10:36 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9024
Sewer Name
20 20TH STREET EAST TRUNK
City
PALMDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
07
Purpose
Routine Assessment
Project
WO_896099_TV20003_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
20 0208
Downstream MH
20 0207
Dir. of Survey
Downstream
Length Surveyed
330.3 ft.
Total Length
330.3 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
3
Overall Quick
Overall Rating
325
Pipe schematic from manhole 20 0208 to 20 0207
MH: 20 0208MH: 20 0207downstream0 ft. AMH - Upstream Manhole, Survey Begins - 20 02080 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area1.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"38.3 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"85.4 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"88.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"134.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"137.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"183.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"186.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"234.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"236.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"288.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"291.1 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"329.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish329.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE330.3 ft. AMH - Downstream Manhole, Survey Ends - 20 0207

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    330.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
330.3MGOCOCKROACHES IN MANHOLE
186.6TFC
329.1DAGS
1.2MGOCONNECTION AT MH 3 O'CLOCK
0AMH20 0208
35.5TFC
288.2TF
5.8CM
0MWM
0MWL
236.6TFC
234.1TFC
38.3TFA
134.5TF
85.4TF
137.5TFC
330.3AMH20 0207
291.1TFA
88.6TFC
329.1CM
2DAGS
183.6TFC

Properties (7)

additional_info
630069070721201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2021-07-07T22:36:05-07:00
documentation
PRO PIPE
is_lateral_inspection
false