Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2021, 09:16 AM
  • 18 0620_18 0619_06292021_022445.mp4

Date
06/29/2021
W/O
896578
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00692
PipeID
P14470
Time
2:16 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9059
Sewer Name
18 NORTH PLANT OUTFALL RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_896578_TV18033_JUN2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0620
Downstream MH
18 0619
Dir. of Survey
Downstream
Length Surveyed
107.5 ft.
Total Length
107.5 ft.
Structural Index
4
Structural Quick
5C3C
Structural Rating
168
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
168
Pipe schematic from manhole 18 0620 to 18 0619
MH: 18 0620MH: 18 0619downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 18 06200.4 ft. MWM - Water Mark, 25 %of cross sectional area2.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAG COAT9.9 ft. TF - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"107.5 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK - (POSSIBLY A DROP CONNECTION)107.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish107.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0619107.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
107.5MGOCONNECTION AT THE MH 9 OC'LOCK - (POSSIBLY A DROP CONNECTION)
9.9TF
2.3SRV
0MWL
0MGOACTIVE CONNECTION AT THE MH 9 OC'LOCK
2.3SAP
0AMH18 0620
107.5SRV
107.5AMH18 0619
107.5SAP
0.4MWM
2.3MGOMAG COAT

Properties (7)

additional_info
1649145
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-06-29T02:16:00-07:00
documentation
PROPIPE
is_lateral_inspection
false